location : GT1B (PD1)
1) servicing GMCB (general main circuit breaker)
- GMCB is use to connect or isolate generator transformer from the grid.
- there are 3 unites of GMCB, one for each of the two GT's and ST's.- GMCB uses a hydraulic spring mechanism in order to make or break the circuit.
2) step down the GT1B excitation transformer
generator (15kV) --> excitation transformer (830Vac) --> thyristor (change to DC) --> rotor
3) measure PI at the GMCB
- reading PI (polarization index) must greater than 1.5. it is better if can get greater than 2.
in the GMCB
PI test